Current Transformers: EJH provides a family of current converters with patented technology. These modules are very reliable and high-accuracy class.
ET201
Loop-powered current transducer
ET201 is an AC current transducer (CT) for 4..20 mA current loops (loop powered 2 wires technology). The module's main features are high precision, extremely compact size and wide configurability: eight pre-calibrated ranges, DIP-switch selected. ET201 allows extremely low consumption and low output ripple and quick response to variations.
Order code : |
|
ET201 |
Description: |
|
Loop-powered current transducer |
Power supply: |
|
5..28 Vdc (loop) |
Consumption: |
|
< 50 mW |
Max input: |
|
40 A |
Connections technique: |
|
2 wire loop-powered |
Output: |
|
4..20 mA |
Accuracy: |
|
0,2% |
Dimensions: |
|
38x40x20 mm |
ET201DC
DC Current Transducer to DC current (4..20 mA - loop powered)
ET201DC is an isolated, contact-less loop powered direct current transducer. The device’s function and look are very similar to those of an active standard CT, but with the remarkable feature of measuring the continuous component of the pass-trough current. For its electrical endurance, ease of use and compact dimensions, the ET201DC fits every kind of current measurement to 40 Adc.
Order code : |
|
ET201DC |
Description: |
|
DC Current Transducer to DC current (4..20 mA - loop powered) |
Power supply: |
|
By 4..20 mA loop |
Input: |
|
8 selectable scales mono/bi-polars via DIP-switch from ±5 A to 40 A (continuous) |
Accuracy: |
|
Better than 0,2% |
Extended loop voltage: |
|
6..100 V |
Compact size: |
|
38 x 40 x 20 mm (Ø 12,5 mm) |
Connection: |
|
Direct without external shunt (also for pulsed currents) |
Note: |
|
Patent pending product (new inductive measurement technology) |
ET201DC100
Passive current transducer 100 Adc for 4..20 mA current loop
ET01DC100 is an isolated and passive, contact-less loop powered direct current transducer. The T201DC100 has functions and look very similar to a standard current transformer, but it has stress features of measuring the continuous current component that pass-through it. For its electrical endurance, ease of use and compact dimensions, the T201DC100 fits every kind of current measurement to 100 Adc.
Order code : |
|
T201DC100 |
Description: |
|
Passive current transducer 100 Adc for 4..20 mA current loop |
Input scales: |
|
Monopolar 0..10 A, 0..25 A, 0..50 A, 0..100 A; bipolar -10..0..+10 A, -25..0..+25 A, -10..0..+50 A, -25..0..+100 A |
Isolation: |
|
1,5 kVdc on raw conductor |
Output/Power Suplply: |
|
4 ..20 mA passive current loop |
Accuracy Class: |
|
0,2 |
Connectos: |
|
Faston 6,3 x 0,8 mm for loop 4..20 mA; 17.80 mm hole for current cable |
Dimension: |
|
50 x 52 x 29.8 mm except from Faston connectors |
ET201DCH300
AC/DC contactless TRMS direct and alternate current (± 300 A) transducer, Hall Effect
ET201DCH300 is an isolated, contact-less loop powered AC/DC current transducer with very compact size (overall dimensions less than 96,5 x 68 x 26 mm). The device function and look is very similar to those of an active standard CT, but with the remarkable feature of measuring the TRMS DC and AC component or the bipolar DC component of the current. For its electrical endurance, ease of use and compact dimensions, the ET201DCH300 transducer fit every kind of current measurement up to 300 Adc/Aac and several applications (batteries , battery chargers, solar panels, power units, dc and ac loads etc.).
Order code : |
|
ET201DCH300 |
Description: |
|
AC/DC contactless TRMS direct and alternate current (± 300 A) transducer, Hall Effect |
Power Supply: |
|
12..28 Vdc |
Accuracy Class: |
|
0,5 |
Input Range: |
|
-300..+300 A ac/dc |
Measurment Type: |
|
TRMS or bipolar DC current |
Output Range: |
|
0..10 V |
Settings: |
|
Via DIP switches |
Dimension: |
|
68 x 95 x 25 mm |
ET201DCH100
AC/DC contactless TRMS direct and alternate current (± 100 A) transducer, Hall Effect
ET201DCH100 is an isolated, contact-less loop powered AC/DC current transducer with very compact size (overall dimensions less than 96,5 x 68 x 26 mm). The device function and look is very similar to those of an active standard CT, but with the remarkable feature of measuring the TRMS DC and AC component and the bipolar DC component of the current. For its electrical endurance, ease of use and compact dimensions, the ET201DCH100 transducer fit every kind of current measurement up to 100 Adc/Aac and several applications (batteries , battery chargers, solar panels, power units, dc and ac loads etc.).
Order code : |
|
ET201DCH100 |
Description: |
|
AC/DC contactless TRMS direct and alternate current (± 100 A) transducer, Hall Effect |
Power Supply: |
|
12..28 Vdc |
Accuracy Class: |
|
0,5 |
Input Range: |
|
-100..+100 A ac/dc |
Measurment Type: |
|
TRMS or bipolar DC |
Output Range: |
|
0..10 V |
Settings: |
|
Via DIP switches |
Dimension: |
|
68 x 95 x 25 mm |